Three-Phase Transformers and Autotransformers

Three-phase transformer connections and phase shifts, vector groups, autotransformer copper saving and power transfer, parallel operation and load sharing, and per-unit impedance.

Power systems use three-phase transformers, autotransformers for small voltage changes, and transformers in parallel to share load.

Three-phase connections

ConnectionLine voltage ratioNotes
Y–YN₁/N₂Third-harmonic problems without a neutral or tertiary
Δ–ΔN₁/N₂Can run as open delta (V–V) at 57.7% of the rating
Y–ΔN₁/(√3 N₂)Step-down at the receiving end; 30° shift
Δ–Y√3 N₁/N₂Step-up at the generating end; 30° shift

Vector groups (for example Dyn11) show the phase shift between HV and LV in clock positions of 30° each. Only transformers of the same group can be paralleled.

Open delta (V–V): capacity = √3 × VA of one transformer = 57.7% of the original three-unit delta bank.

Autotransformer

One winding with a tap; part of the power is transferred conductively.

  • With ratio a = V_LV/V_HV (< 1): copper saved = a times that of a two-winding transformer (copper used = 1 − a).
  • Power transferred inductively = (1 − a) × total; conductively = a × total.
  • Rating as an autotransformer = two-winding rating/(1 − a).
  • Disadvantages: no isolation between HV and LV; higher short-circuit current.

Parallel operation

Conditions: same voltage ratio, same polarity, same phase sequence and vector group, and (for good load sharing) similar per-unit impedances and X/R ratios.

Load sharing: each transformer takes a share inversely proportional to its impedance: S₁ = S Z₂/(Z₁ + Z₂) (with impedances in ohms on a common base). Transformers with equal per-unit impedance share load in proportion to their ratings.

Per-unit values

Z_pu = Z_actual/Z_base, with Z_base = V_base²/S_base. A transformer has the same per-unit impedance on both sides. Change of base: Z_new = Z_old (S_new/S_old)(V_old/V_new)².

Worked example

A 230/115 V two-winding transformer rated 10 kVA is connected as a 345/230 V autotransformer.

  • a = 230/345 = 2/3; autotransformer rating = 10/(1 − 2/3) = 30 kVA.

Practice

GATE-styleNAT · numerical answer

An autotransformer steps 400 V down to 300 V. What fraction of the copper of an equivalent two-winding transformer does it save?

Show answer and explanationAnswer: 0.75

Copper saved = a = V_LV/V_HV = 0.75.

GATE-styleNAT · numerical answer

Three 100 kVA transformers in delta lose one unit and run in open delta. What load (kVA) can the bank supply? (Give 1 decimal place.)

Show answer and explanationAnswer: 173.2

V–V capacity = √3 × 100 = 173.2 kVA (57.7% of 300 kVA).

GATE-styleNAT · numerical answer

Two transformers in parallel have impedances 2 Ω and 3 Ω (same angle). They share a 500 kVA load. How much (kVA) does the 2 Ω unit carry?

Show answer and explanationAnswer: 300

S₁ = S Z₂/(Z₁ + Z₂) = 500 × 3/5 = 300 kVA.

GATE-styleMCQ · one correct answer

A star-delta transformer introduces a phase shift between primary and secondary line voltages of:

Show answer and explanationAnswer: B

Y–Δ and Δ–Y connections shift the line voltages by 30°.