Synchronous Generators and Motors
EMF equation with winding factors, synchronous reactance, phasor diagram, voltage regulation methods, power-angle characteristic, parallel operation and synchronisation, V-curves and synchronous motor starting.
Synchronous machines run at exactly synchronous speed. Almost all the world's electricity comes from synchronous generators (alternators); synchronous motors are used where constant speed or power factor control is needed.
EMF equation
E_ph = 4.44 f N_ph Φ K_w, with winding factor K_w = K_p K_d:
- Pitch factor K_p = cos(α/2) (α = short-pitch angle).
- Distribution factor K_d = sin(mβ/2)/(m sin(β/2)) (m slots per pole per phase, β = slot angle).
- Short pitching reduces harmonics: to eliminate the nth harmonic, short-pitch by 180°/n.
Equivalent circuit and regulation
Per phase: E = V + I_a(R_a + jX_s), where X_s (synchronous reactance) = leakage reactance + armature reaction reactance.
- Voltage regulation = (E − V)/V. It is positive for lagging and unity pf, and can be negative for leading pf.
- Methods: EMF (synchronous impedance) method (pessimistic), MMF method (optimistic), ZPF (Potier) method (most accurate).
- From open- and short-circuit tests: Z_s = (open-circuit voltage)/(short-circuit current) at the same field current. Short-circuit ratio (SCR) = 1/X_s (per unit).
Power–angle characteristic
For a cylindrical rotor (R_a neglected):
P = (3 E V/X_s) sin δ (δ = load or power angle)
- Maximum power at δ = 90° (steady-state stability limit).
- Salient pole machines add a reluctance power term (V²/2)(1/X_q − 1/X_d) sin 2δ, so their maximum is at δ < 90°.
Parallel operation (synchronising)
Before connecting to the bus: same voltage, frequency, phase sequence and phase angle (checked with synchroscope or lamps). Once connected:
- Changing the prime-mover input changes the real power (and δ).
- Changing the field excitation changes the reactive power (and pf).
Synchronous motor
- Not self-starting (uses damper windings to start as an induction motor, or a pony motor).
- V-curves: armature current against field current at constant load; minimum current at unity pf.
- Over-excited: leading pf, supplies reactive power (a synchronous condenser for pf correction). Under-excited: lagging pf.
Worked example
A 3-phase alternator: 50 Hz, 100 turns per phase, flux 0.05 Wb, K_w = 0.95.
- E_ph = 4.44 × 50 × 100 × 0.05 × 0.95 = 1054.5 V.
Practice
A coil is short-pitched by 30°. What is its pitch factor? (Give 4 decimal places.)
Show answer and explanation
Answer: 0.9659K_p = cos(α/2) = cos 15° = 0.9659.
An alternator has E = 1.2 pu, V = 1.0 pu and X_s = 0.8 pu (per phase, per unit power). What is its maximum power in pu?
Show answer and explanation
Answer: 1.5P_max = EV/X_s = 1.2/0.8 = 1.5 pu at δ = 90°.
An over-excited synchronous motor operates at:
Show answer and explanation
Answer: AOver-excitation makes the motor supply reactive power, so it draws a leading current.
For an alternator connected to an infinite bus, increasing the field excitation mainly changes its:
Show answer and explanation
Answer: BReal power is set by the prime mover; excitation changes E and hence the reactive power.