Heat Exchangers: LMTD and Effectiveness-NTU

Types of heat exchangers, parallel and counter flow, log mean temperature difference, fouling, capacity ratio, effectiveness and NTU method, and boiling and condensation basics.

A heat exchanger moves heat from a hot fluid to a cold one across a wall. Two methods size and rate them: LMTD when all temperatures are known, and effectiveness–NTU when the outlet temperatures are not.

Types

  • Parallel flow: both fluids enter at the same end. The cold outlet can never be hotter than the hot outlet.
  • Counter flow: opposite ends. The most effective arrangement; the cold outlet can exceed the hot outlet.
  • Cross flow (car radiators) and shell-and-tube exchangers use correction factors.

LMTD method

Q = U A ΔT_lm, with

ΔT_lm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂)

  • Parallel flow: ΔT₁ = T_h,in − T_c,in; ΔT₂ = T_h,out − T_c,out.
  • Counter flow: ΔT₁ = T_h,in − T_c,out; ΔT₂ = T_h,out − T_c,in.
  • If ΔT₁ = ΔT₂ (a balanced counter-flow exchanger), ΔT_lm = ΔT.
  • For the same terminal temperatures, counter flow gives a larger LMTD, so it needs less area.

Fouling (deposits on the surfaces) adds resistance: 1/U = 1/h_i + R_f + 1/h_o (thin wall).

Effectiveness–NTU method

  • Heat capacity rates: C_h = ṁ_h c_h, C_c = ṁ_c c_c. C_min is the smaller.
  • Capacity ratio C = C_min/C_max.
  • Q_max = C_min (T_h,in − T_c,in).
  • Effectiveness ε = Q/Q_max.
  • NTU = UA/C_min.
Arrangementε
Parallel flow[1 − exp(−NTU(1 + C))]/(1 + C)
Counter flow[1 − exp(−NTU(1 − C))]/[1 − C exp(−NTU(1 − C))]
Any type with C = 0 (condenser or evaporator)1 − exp(−NTU)
Counter flow with C = 1NTU/(1 + NTU)

Boiling and condensation

  • Pool boiling curve: natural convection → nucleate boiling (very high h) → critical heat flux → transition → film boiling. Operating beyond the critical heat flux can burn out the surface.
  • Condensation: dropwise condensation gives much higher h than filmwise. Nusselt's theory gives filmwise h on vertical plates.

Worked example

Hot oil cools from 150 °C to 90 °C while water heats from 30 °C to 70 °C, in counter flow, with U = 300 W/m²·K and Q = 60 kW.

  • ΔT₁ = 150 − 70 = 80; ΔT₂ = 90 − 30 = 60; ΔT_lm = 20/ln(80/60) = 69.5 K.
  • A = 60,000/(300 × 69.5) = 2.88 m².

Practice

GATE-styleNAT · numerical answer

A condenser (C = 0) has NTU = 2. What is its effectiveness? (Give 3 decimal places.)

Show answer and explanationAnswer: 0.865

ε = 1 − e^(−NTU) = 1 − e⁻² = 0.865.

GATE-styleNAT · numerical answer

In a counter-flow exchanger the terminal temperature differences are 40 K and 40 K. What is the LMTD in K?

Show answer and explanationAnswer: 40

When ΔT₁ = ΔT₂ the LMTD equals that difference (the limit of the formula).

GATE-styleNAT · numerical answer

A counter-flow exchanger with C = 1 has NTU = 3. What is its effectiveness?

Show answer and explanationAnswer: 0.75

ε = NTU/(1 + NTU) = 3/4 = 0.75.

GATE-styleNAT · numerical answer

Hot fluid enters at 200 °C and cold at 50 °C; C_min = 2 kW/K. What is the maximum possible heat transfer in kW?

Show answer and explanationAnswer: 300

Q_max = C_min (T_h,in − T_c,in) = 2 × 150 = 300 kW.

GATE-styleMCQ · one correct answer

For the same inlet and outlet temperatures, which arrangement needs the smallest area?

Show answer and explanationAnswer: A

Counter flow gives the largest LMTD, so for the same Q and U it needs the least area.