Heat Exchangers: LMTD and Effectiveness-NTU
Types of heat exchangers, parallel and counter flow, log mean temperature difference, fouling, capacity ratio, effectiveness and NTU method, and boiling and condensation basics.
A heat exchanger moves heat from a hot fluid to a cold one across a wall. Two methods size and rate them: LMTD when all temperatures are known, and effectiveness–NTU when the outlet temperatures are not.
Types
- Parallel flow: both fluids enter at the same end. The cold outlet can never be hotter than the hot outlet.
- Counter flow: opposite ends. The most effective arrangement; the cold outlet can exceed the hot outlet.
- Cross flow (car radiators) and shell-and-tube exchangers use correction factors.
LMTD method
Q = U A ΔT_lm, with
ΔT_lm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂)
- Parallel flow: ΔT₁ = T_h,in − T_c,in; ΔT₂ = T_h,out − T_c,out.
- Counter flow: ΔT₁ = T_h,in − T_c,out; ΔT₂ = T_h,out − T_c,in.
- If ΔT₁ = ΔT₂ (a balanced counter-flow exchanger), ΔT_lm = ΔT.
- For the same terminal temperatures, counter flow gives a larger LMTD, so it needs less area.
Fouling (deposits on the surfaces) adds resistance: 1/U = 1/h_i + R_f + 1/h_o (thin wall).
Effectiveness–NTU method
- Heat capacity rates: C_h = ṁ_h c_h, C_c = ṁ_c c_c. C_min is the smaller.
- Capacity ratio C = C_min/C_max.
- Q_max = C_min (T_h,in − T_c,in).
- Effectiveness ε = Q/Q_max.
- NTU = UA/C_min.
| Arrangement | ε |
|---|---|
| Parallel flow | [1 − exp(−NTU(1 + C))]/(1 + C) |
| Counter flow | [1 − exp(−NTU(1 − C))]/[1 − C exp(−NTU(1 − C))] |
| Any type with C = 0 (condenser or evaporator) | 1 − exp(−NTU) |
| Counter flow with C = 1 | NTU/(1 + NTU) |
Boiling and condensation
- Pool boiling curve: natural convection → nucleate boiling (very high h) → critical heat flux → transition → film boiling. Operating beyond the critical heat flux can burn out the surface.
- Condensation: dropwise condensation gives much higher h than filmwise. Nusselt's theory gives filmwise h on vertical plates.
Worked example
Hot oil cools from 150 °C to 90 °C while water heats from 30 °C to 70 °C, in counter flow, with U = 300 W/m²·K and Q = 60 kW.
- ΔT₁ = 150 − 70 = 80; ΔT₂ = 90 − 30 = 60; ΔT_lm = 20/ln(80/60) = 69.5 K.
- A = 60,000/(300 × 69.5) = 2.88 m².
Practice
A condenser (C = 0) has NTU = 2. What is its effectiveness? (Give 3 decimal places.)
Show answer and explanation
Answer: 0.865ε = 1 − e^(−NTU) = 1 − e⁻² = 0.865.
In a counter-flow exchanger the terminal temperature differences are 40 K and 40 K. What is the LMTD in K?
Show answer and explanation
Answer: 40When ΔT₁ = ΔT₂ the LMTD equals that difference (the limit of the formula).
A counter-flow exchanger with C = 1 has NTU = 3. What is its effectiveness?
Show answer and explanation
Answer: 0.75ε = NTU/(1 + NTU) = 3/4 = 0.75.
Hot fluid enters at 200 °C and cold at 50 °C; C_min = 2 kW/K. What is the maximum possible heat transfer in kW?
Show answer and explanation
Answer: 300Q_max = C_min (T_h,in − T_c,in) = 2 × 150 = 300 kW.
For the same inlet and outlet temperatures, which arrangement needs the smallest area?
Show answer and explanation
Answer: ACounter flow gives the largest LMTD, so for the same Q and U it needs the least area.