Faults and Symmetrical Components

Symmetrical three-phase faults and fault MVA, sub-transient and transient reactances, symmetrical components, sequence networks, and line-to-ground, line-to-line and double line-to-ground faults.

A fault (short circuit) draws very large currents. Fault studies size circuit breakers and set protection.

Symmetrical (three-phase) faults

  • With pre-fault voltage 1 pu and Thevenin impedance Z_th at the fault: I_f = 1/Z_th pu.
  • Fault MVA = S_base/Z_th(pu) = √3 V_L I_f.
  • A generator's reactance rises after the fault: sub-transient X″_d (first cycles) < transient X′_d < synchronous X_d (steady state). Breakers are rated using X″_d.
  • Current-limiting reactors reduce fault levels.

Symmetrical components

Any unbalanced set of three phasors = sum of three balanced sets:

  • Positive sequence (abc rotation), negative sequence (acb), zero sequence (all in phase).
  • With operator a = 1∠120°: I_a0 = (I_a + I_b + I_c)/3, I_a1 = (I_a + a I_b + a² I_c)/3, I_a2 = (I_a + a² I_b + a I_c)/3.
  • 1 + a + a² = 0.
  • Zero-sequence current flows only if there is a return path (grounded neutral); the neutral carries 3I₀. Delta windings block zero sequence from the lines.

Unsymmetrical faults (unloaded generator, E = 1 pu)

FaultConnection of sequence networksFault current
Single line-to-ground (LG)Series: Z₁ + Z₂ + Z₀ (+ 3Z_f)I_f = 3E/(Z₁ + Z₂ + Z₀ + 3Z_f)
Line-to-line (LL)Positive and negative in parallelI_f = √3 E/(Z₁ + Z₂)
Double line-to-ground (LLG)Negative ∥ zero, in series with positiveI_a1 = E/(Z₁ + Z₂Z₀/(Z₂ + Z₀))

For a solidly grounded generator with Z₀ small, the LG fault can be larger than the three-phase fault. Grounding the neutral through a reactance limits it.

Worked example

A generator has Z₁ = Z₂ = j0.2 pu and Z₀ = j0.1 pu, solidly grounded.

  • Three-phase fault: 1/0.2 = 5 pu.
  • LG fault: 3/(0.2 + 0.2 + 0.1) = 6 pu.
  • LL fault: √3/0.4 = 4.33 pu.

Practice

GATE-styleNAT · numerical answer

A bus has a Thevenin reactance of 0.1 pu on a 100 MVA base. What is its fault level in MVA?

Show answer and explanationAnswer: 1000

Fault MVA = S_base/X_th = 100/0.1 = 1000 MVA.

GATE-styleNAT · numerical answer

For the bus above at 11 kV, what is the three-phase fault current in kA? (Give 2 decimal places.)

Show answer and explanationAnswer: 52.49

I = 1000 MVA/(√3 × 11 kV) = 52.49 kA.

GATE-styleNAT · numerical answer

The phase currents are I_a = 10, I_b = 0 and I_c = 0 A. What is the zero-sequence current in A? (Give 3 decimal places.)

Show answer and explanationAnswer: 3.333

I₀ = (I_a + I_b + I_c)/3 = 10/3 = 3.333 A (and I₁ = I₂ = 3.333 A too).

GATE-styleMCQ · one correct answer

Which fault involves all three sequence networks connected in series?

Show answer and explanationAnswer: A

In an LG fault, I_a1 = I_a2 = I_a0, so the three networks carry the same current in series.